Appendix B. Status Table and Settings
513
Table 117. Status-Table Fields and Descriptions
Fieldname Description Variable Type Default Range Edit? Info Type
CommConfig
16
Array of values telling the
configuration of comm ports.
Aliased to:
CommConfigRS-232
CommConfigME
CommConfigCOM310
CommConfigSDC7
CommConfigSDC8
CommConfigSDC10
CommConfigSDC11
CommConfigCOM1
CommConfigCOM2
Integer array of 9
RS-232
through
SDC8
= 4 (Enabled)
COM1 or
COM2 = 0
(Disabled)
0 = Program
Disabled
4 = Program
Enabled
Ports toggled
through program
control
(SerialOpen /
SerialClose).
RS-232 is
always
hardware-
enabled.
Config
Baudrate
17
Array of baud rates for
comms. Aliased to:
BaudrateRS-232
BaudrateME
BaudrateSDC
BaudrateCOM1
BaudrateCOM2
Integer array of 9
RS-232=-
115200 ME-
SDC8 =
115200
COM1 or
COM2 = 0
(Disabled)
0 = Auto
1200
2400
4800
9600
19.2k
38.4k
57.6k
115.2k
Yes, can also
use SerialOut
instruction to
setup.
Config
IsRouter
Is the CR800 configured to
act as router?
Boolean False 0 or 1 Yes Config PB
PakBusNodes (p. 413)
Number of nodes
(approximately) that will
exist in the PakBus network.
This value is used to
determine how much
memory to allocate for
networking (see
CommsMemFree(2)
(p. 413) ).
Integer 50 >=50 Yes Config PB
CentralRouters
18
Array of (8) PakBus
addresses for central routers.
Integer array of 8 0 Yes Config PB