Campbell-scientific CR800 and CR850 Measurement and Control Systems Instrukcja Użytkownika Strona 108

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 107
Section 7. Installation
108
For more detailed information on Network Planner, please consult the LoggerNet
manual, which is available at www.campbellsci.com.
7.6.3.5.2 Basics
PakBus Settings
Device a
ddresses are automatically allocated but can be changed.
Device connections are used to determine whether neighbor lists should be
specified.
Verification intervals will depend on the activities between devices.
Beacon intervals will be assigned but will have default values.
Network role (e.g., router or leaf node) will be assigned based on device
links.
Device Links and Communication Resources
Disallow links that will not work.
Comparative desirability of links.
Prevent over-allocation of resources.
Optimal RS-232 and CS I/O ME baud rates based on device links.
Optimal packet size limits based upon anticipated routes.
Fundamentals of Planning a Network
Add a background (optional).
Place stations, peripherals, etc.
Establish links.
Set up activities (scheduled poll, callback).
Configure devices.
Configure LoggerNet (adds the planned network to the LoggerNet Network
Map).
7.7 Programming
Programs are created with either Short Cut (p. 443) or CRBasic Editor (p. 109).
Programs can be up to 490 kB in size; most programs, however, are much smaller.
7.7.1 Writing and Editing Programs
7.7.1.1 Short Cut Editor and Program Generator
Short Cut is easy-to-use, menu-driven software that presents the user with lists of
predefined measurement, processing, and control algorithms from which to
choose. The user makes choices, and Short Cut writes the CRBasic code required
to perform the tasks. Short Cut creates a wiring diagram to simplify connection of