Campbell-scientific CS10-L and CS15-L Current Transformers Instrukcja Użytkownika Strona 8

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 30
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 7
CS10-L and CS15-L Current Transformers
Specifications
Measurement Ranges: 0.15 to 200 A (CS10)
0.15 to 125 A (CS15)
Frequency: 50 and 60 Hz
Insulation Resistance: 100 M ohm @ 500 VDC
High Potential: 2000 volts
Rated Current: 200 A (CS10), 125 A (CS15)
Storage Temperature: -25ºC to 70ºC
Operating Temperature: -25ºC to 55ºC
Case Material: Polypropylene Resin
Construction: Epoxy Encapsulated
Accuracy with 10 ohm
burden max. (resistive): typically ±5 percent of actual value with
provided multiplier
Dimensions: Outer diameter: 1.89” (4.8 cm)
Inner diameter: 0.75” (1.9 cm)
Height: 0.67” (1.7 cm)
3. Installation
Place one AC load wire through the hole of the CS10-L or CS15-L (see Figure
2).
FIGURE 2. AC load wire installed in CS10 (color of ac load wire can
vary)
2
Przeglądanie stron 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 29 30

Komentarze do niniejszej Instrukcji

Brak uwag