SDM-AO4 Four Channel Analog Output
12
16: Z=X+F (P34) ; Add 360 to the current reading
1: 9 X Loc [ WD_0_540 ] ; otherwise, the current reading
2: 360 F ; is left alone
3: 9 Z Loc [ WD_0_540 ]
17: End (P95)
18: End (P95)
; Scale the measurements for the SDM-AO4 to output 0 to 1000 mV
19: Z=X*F (P37) ; Scale WS: 0-50 mps = 0-1000 mV
1: 1 X Loc [ WS_ms ]
2: 20 F
3: 5 Z Loc [ WSoutput ]
20: Z=X*F (P37) ; Scale WD: 0-540 deg = 0-1000 mV
1: 9 X Loc [ WD_0_540 ]
2: 1.859 F
3: 6 Z Loc [ WDoutput ]
21: Z=X+F (P34) ; Scale Temperature: -40-60 deg C = 0-1000 mV
1: 3 X Loc [ Temp_C ]
2: 40 F
3: 7 Z Loc [ TempOut ]
22: Z=X*F (P37)
1: 7 X Loc [ TempOut ]
2: 10 F
3: 7 Z Loc [ TempOut ]
23: Z=X*F (P37) ; Scale RH: 0-100 % RH = 0-1000 mV
1: 4 X Loc [ RH ]
2: 10 F
3: 8 Z Loc [ RHout ]
; Send mV outputs to SDM-AO4
24: SDM-AO4 (P103)
1: 4 Reps
2: 30 SDM Address
3: 5 Loc [ WSoutput ]
End Program