Campbell-scientific LoggerNet Datalogger Support Software Instrukcja Użytkownika Strona 479

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 580
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 478
Section 14. Troubleshooting Guide
14.8 Troubleshooting PakBus Communications
For additional information on PakBus communication, refer to our PakBus
Networking Guide (under separate cover).
Problem: LoggerNet cant communicate with in-range PakBus datalogger
(PC-RF400~~~RF400-CR510PB~~~ RF400-CR510PB~~~CR205)
Possible reason 1: LoggerNets PakBus Address for datalogger
doesnt match dataloggers PakBus Address.
Remedy 1: Make them match.
Possible reason 2: An RF400 Series radio is set to a different
Hopping Sequence, Network Address, Radio Address, or Standby
Mode.
Remedy 2: Set both radios exactly the same in the above parameters.
(‘baseradios Active Interface is typically Auto Sense, remote radio
is typically CSDC 7)
Possible reason 3: No PakBusPort in device map between root and
datalogger.
Remedy 3: Add PakBusPort.
Possible reason 4: No PakBus OS in datalogger
Remedy 4: If you have two in-range routers using neighbor filters, in
order for them to discover one another you must list each of them as a
potential neighbor in the others neighbor filter.
Problem: LoggerNet cant communicate via datalogger-router to a certain
remote datalogger.
(PC-RF400~~~RF400-CR10XPB~~~RF400-CR510~~~CR205)
Possible reason 1: A datalogger router has insufficient *D15 max
nodes, max neighbors, or max routers configured.
Remedy 1: Increase the *D15 numbers.
*D15 settings of 000x, 6, 6, 6, 0 are reasonable for a router in a
network of under a half dozen nodes
*D15 settings allocate memory similar to *A. It is a good idea, when
configuring *D15 settings, to leave room to grow.Changing *D15
settings later on could result in loss of data as *0 is entered to compile
new settings.
Possible reason 2: Last datalogger router has no means configured of
discovering the remote datalogger.
Remedy 2: Configure the datalogger router with either a neighbor
filter or a beacon. Make sure Neighbor Filter potential neighbors
14-17