DataView (CD294) Dual Line Data Display
5. Mounting in Enclosure Door
Use the template provided to mark out the four mounting holes and cut-
out for the CD294. Drill the four corner holes using a 4.5 mm drill and
cut out the mounting hole using a jig-saw or nibbler. Use the screws and
nuts provided to attach the CD294, ensuring that the rubber o-ring is
located correctly in the o-ring groove to provide sealing.
6. Shipping Kit
The CD294 DataView Shipping Kit includes:
1. CD294 DataView display with data cable
2. Custom CD294 programming cable
3. Compact Disc containing PC294 programming software, CD294 Manual,
SDS511 manual and example software
4. CD294 MountingTemplate
5. 4 x Mounting screws, nuts, metal washers and sealing washers
6. 2 mm silicon o-ring
7. Hardware
SPECIFICATIONS
Physical
Width: 130 mm
Height: 100 mm
Depth: 25 mm
Weight: 150 g
Supply Requirements: 5 VDC (Powered from datalogger)
Power
Current consumption:
Operating: 5.5 mA typical while display is active
Quiescent: <100 μA