Przeglądanie stron 22
AM16/32A Relay Analog Multiplexer
*1 Table 1 Programs
1: 60 Sec. Execution Interval
;ACTIVATES MULTIPLEXER
1: Do (P86)
1: 41 Set high Port 1
2: Excitation with Delay (P22)
1: 1 Ex Channel
2: 0 Delay w/Ex (0.01 sec units)
3: 15 Delay after Ex (0.01 sec units)
4: 0 mV Excitation
;BEGINS STRAIN GAGE MEASUREMENT LOOP
3: Beginning of Loop (P87)
1: 0 Delay
2: 10 Loop Count
;CLOCK PULSE
4: Do (P86)
1: 72 Pulse Port 2
;DELAY
5: Excitation with Delay (P22)
1: 1 EX Chan
2: 0 Delay w/EX (units=.01sec)
3: 1 Delay after EX (units=.01sec)
4: 0 mV Excitation
;FULL BRIDGE MEASUREMENT INSTRUCTION
6: Full Bridge (P6)
1: 1 Rep
2: 3 50 mV slow Range
3: 1 IN Chan
4: 1 Excite all reps w/Enchain 1
5: 5000 mV Excitation
6: 1-- Loc [:STRAIN #1]
7: 1 Mult
8: 0 Offset
;END OF STRAIN GAGE MEASUREMENT LOOP
7: End (P95)
;BEGINNING OF POTENTIOMETER MEASUREMENT LOOP
8: Beginning of Loop (P87)
1: 0 Delay
2: 6 Loop Count
9: Step Loop Index (Extended) (P90)
1: 2 Step
;CLOCK PULSE
10: Do (P86)
1: 72 Pulse Port 2
17
Przeglądanie stron 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 45 46