A6REL-12 Relay Driver
6
5.2 EDLOG
Although the following example is a 21X program, other dataloggers that use
Edlog such as the CR10(X) and CR23X are programmed similarly.
*1 Table 1 Program
01: 5 Sec. Execution Interval
1: Panel Temperature (P17) Measure the TC
1: 1 Loc [:REF TEMP ] reference temperature
2: Thermocouple Temp (DIFF) (P14)
1: 1 Rep Measure
2: 1 5 mV slow Range temperature
3: 1 IN Chan
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp Loc REF TEMP
6: 2 Loc [:TEMP ]
7: 1.8 Mult
8: 32 Offset
3: If X<=>F (P89) If temp is greater
1: 2 X Loc TEMP than or equal to
2: 3 >= 99, set Flag 1 low
3: 99 F
4: 21 Reset flag 1
4: If X<=>F (P89) If temp is less
1: 2 X Loc TEMP than 96, set
2: 4 < Flag 1 high
3: 96 F
4: 11 Set flag 1
5: Set Port (P20) Set Port 1
1: 11 Set according to flag 1 according to
2: 1 Port Number Flag 1
Input Location Labels:
1:REF TEMP 2:TEMP