Campbell-scientific SDM-CD16S 16-Channel Solid State DC Relay Controll Instrukcja Użytkownika Strona 15

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 30
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 14
SDM-CD16S 16 Channel Solid State DC Control Module
The Example 1 program uses an array of values to set the SDM-CD16S control
outputs:
Program name: SDMCD16Example1.CR1
'Date written: 6/25/2007
'\\\\\\\\\\\\\\\\\\\\\\\\\ DECLARATIONS /////////////////////////
Public Flag(8) as boolean
Public I
Public Temp(5)
Public Heat(5)
Public Cool(5)
Public Fan(5)
'Note CD16_Output(I), I = 1 to 5 are for Heat, I = 6 to 10 are for ‘Cooling, I= 11 to 15 are for Fans
Dim CD16_Output(16)
'\\\\\\\\\\\\\\\\\\\\\\\\\\\ PROGRAM ////////////////////////////
BeginProg
Scan(5,Sec, 3, 0)
For I = 1 to 5
If (Temp(I) < 23.5) Then
Heat(I) = 1
ElseIf (Temp(I) >= 25.5) Then
Heat(I) = 0
EndIf
If (Temp(I) >= 27.5) Then
Cool(I) = 1
ElseIf (Temp(I) < 24.5) Then
Cool(I) = 0
EndIf
If (Heat(I) <> 0) OR (Cool(I) <> 0) Then
Fan(I) = 1
Else
Fan(I) = 0
EndIf
Next I
If TimeInToInterval(10,15,Min) Then Flag(2) = True
If TimeInToInterval(0,15,Min) Then Flag(2) = False
If Flag(2) = True then
For I = 1 to 5
Fan(I) = 1
Next I
EndIf
For I = 1 to 5
CD16_Output(I) = Heat(I)
CD16_Output(I+5) = Cool(I)
CD16_Output(I+10) = Fan(I)
Next I
SDMCD16AC(CD16_Output(), 1, 0)
NextScan
EndProg
11
Przeglądanie stron 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 29 30

Komentarze do niniejszej Instrukcji

Brak uwag